What kind of pipes are suitable for hidden lightning rod into facade?
According to the old, no longer valid standard, a non-metallic unbreakable pipe having a lightness (inside diameter) of min 29 mm had to be used for the hidden lightning rod.
This standard has not been valid for many years, but still many people demand pipes.
As a producer, we recommend using pipes with a medium mechanical resistance of 750N / 5cm.
The most suitable flexible wiring pipe is SUPER MONOFLEX 1240, which has an internal diameter of min. 31.2 mm.
What kind of boxes can we mounting into the wood (flammable substrates)?
What is wood really? And can we install the box in C3? Our answer is:
Currently it is difficult to install the box on or into the C3 materials because the standard ČSN 33 2312 / Z1 provide with respect to ČSN EN 13 501-1 the end of sorting of materials to the degree of flammability and converts this classification into reaction to fire classes. Uncertainty about whether I can install wiring boxes comes from C3 materials, we mention the transfer of C3 flammability materials. We only mention the transfer of C3 flammability grade materials. Since June 2005, these materials have been identified as materials of the reaction class E or F.
The wood has never been in this category. Hard wood, such as beech or oak, was even hardly flammable in the C1 flammability grade. It is understandable that each wood is finally surface-treated and this surface can increase its flammability. In order to avoid similar assumptions, we will always have in mind materials of reaction to fire class F. This classification must be provided by each manufacturer of the construction product.
And now to the standard ČSN 33 2312 Electrical equipment in and on flammable substances. The above-mentioned amendment to Z1 introduces a paragraph in the introductory paragraph of the original standard ČSN 33 2312 of 8.5.1985, which refers to the current validity of this standard together with the standard ČSN EN 60670-1-Box and complete covers for electrical accessories for residential and similar solid electric installation. This standard will replace the standard from 1.10.2007 for the standard ČSN 33 2312.
Classification 7.2 according to the method of installation - 7.2.1 Embedded, semi-enclosed or put in 7.2.1.2 such as flammable walls, flammable ceilings or flammable floors to be followed by sorting according to 7.2.1.3, such as hollow walls, hollow ceilings, hollow floors or furniture. We have mentioned these sorts just because KOPOS KOLIN a.s. produce wiring boxes into hollow wall (in ocher color), tested and classified according to these classifications. From the 850 ° C flaming loop test and the above classification, we can clearly recommend mounting on wiring boxes into hollow walls to materials of reaction to fire class F.
And because, according to the standard, there is no more flammable substance, there is no concern about the possibility of installing our boxes into hollow walls on the construction material with any reaction to fire.
What is the different between mars and jupiters cables?
These names are distinguished by dimensional series of cable trays.
MARS cable trays have the traditional dimensions used on the Czech market with a side height of 50 and 100 mm and widths of 62, 125, 250 and 500 mm. The total length of the trays is 2.1 m.
The JUPITER cable trays are produced according to standard European dimensions. These trays have a side height of 35, 60, 85 or 110 mm and are available in widths of 50, 100, 150, 200, 300, 400, 500 and 600 mm. The standard length of the tray is 3 m.
What are the classes of possibilities to fiill with soil protectors KOPOFLEX or KOPODUR?
The standard ČSN 73 30 50 divided soil into a total of 7 following classes. The summary gives a simplified feature.
Class | Soil characteristics |
1 | Compact soil of soft consistency and incompact loose soil with gravel grains up to 5 cm (max. 10 % volume) |
2 | Compact soil of ridgit consistency and medium lying down of soil with gravel grains up to 10 cm |
3 | Compact soil of solid - ridgit consistency, clay soil with soft – ridget consistency and incompact lying down of soil, gravel grains up to 10 cm, cement gravel and weathered rock |
4 | Clay gravel solid – ridget consistency, rough gravel with grains up to 25 cm and bouldery component up to 0,1 m3, gravels with clay cement, weathered rock |
5 | Rough gravel grains 10 – 25 cm, incompact soil of 4 th class with clay cement solid consistency. Healthy weathered rock |
6 | Strengthened weathered rock, incompact soil with bouldery up to 0,1 m3 |
7 | Healthy rocks |
Accurate definition of 1st class according to KOPOS KOLIN a.s. recommends that the KOPOFLEX and KOPODUR shields are covered with soil with grains up to 50 mm in a maximum volume of 10% in soil. The detailed conditions are determined by EN 1610, which replaces an already invalid ČSN 73 30 50. Here is a description of the soil, which is already ivalid according to the standard but it describes the exact nature of the soil.
a) Compact, soft consistency. E.g. arable land, clay, sand clay, muddy sand
b) incompact, loose grains of up to 20 mm with grains over 20 to 50 mm in volume up to 10% of the total volume of first class soil eg sand, sand with gravel, sand gravel, small and medium gravel or gravel with stones
c) construction waste and weights of a similar nature to soil classified as first class
How many meters are used KPS - cover of cable clamps SONAP?
Every 3.5 m (going up the floor) and it is only a mechanical barrier against spontaneous cable breakage in case of fire (does not use as a fire plug).
Do you have a fire resistant dowels into the gypsum walls?
No.
Do the cable trays meet the requirements for electrical continuity?
The tray system is designed to provide good interconnection when joining individual trays. This is achieved with a fixed connection using special NSM 6X10 screws.
The claim is based on the test report concerning cable routes and cable ladders classed under to ČSN EN 61537 standard pursuant to Article 6.3.2 as cable routes with the characteristics of electrical continuity to ensure protective bonding and ground connection. Under to Article 11.1.2, an AC current of 25 ± 1 A with a frequency of 50 Hz to 60 Hz is fed along the length of the test samples. The test performed under this article was compliant. Impedance on the circuit board is less than 50 Mω. The cable trays and cable ladders were also found to be compliant during the test.
Can we use Omega clamps and clamps 67xx as a rising route?
Yes.
Can we connect more cores into one fire resistant ceramic clamp?
Yes.
Can kopos fire resistant systems mounted on material another producer?
Yes, if the anchor element has a fire resistence certification.
?Qué presión se puede emplear al introducir conductos en tubos protectores HDPE?
Los tubos protectores del cable óptico HDPE se ensayan por una presión de 1,5 MPa durante 2 horas. Al introducir los conductos en práctica se suele utilizar la presión de 1 hasta 1,2 Mpa.
?Qué es un material libre de halógenos? ?En qué difiere un material libre de halógenos del PVC?
Un material libre de halógenos es tal material que no contiene el grupo de elementos halógenos (flúor, cloro, bromo, yodo, astato). Estos elementos liberan durante la combustión sustancias que son en la forma de humo tóxico peligrosas para el hombre y al mismo tiempo causan la corrosión de metales. Los plásticos libres de halógenos son en este sentido más seguros y productos de ello son adecuados sobre todo para las zonas destinadas a reuniones y salidas de escape (espacios públicos, estaciones de trenes y autobuses, teatros, cines, centros comerciales etc.) PVC o sea polivinilclorido no es un material libre de halógenos debido a que contiene cloro.
?De qué modo se pueden segregar y blindar redes de fuerzas y datos en minicanales?
La empresa KOPOS ofrece varias soluciones de cómo segregar, blindar y al mismo tiempo disponer los conductos en los minicanales: separadores de plástico PEKE 60 a PEP 60, separador de plástico con hoja metálica PKS 70/60, separador de metal PEP 60/K y canales de blindaje SK 40x20 y SK 40x33:
- separador PEKE 60 sirve a segregar el espacio interior de canales de instalación eléctrica y con ello a un manejo más fácil de los cables introducidos y a verlos mejor
- separador con hoja metálica PKS 70/60 es una modificación del separador PEKE 60. Gracias a una hoja de lámina fina tiene características similares a un separador metálico pero es más ligero. Los separadores PKS 70/60 se deben conectar entre sí. Para ello se utiliza un cable de conexión PLSK.
- PEP 60 es un nuevo tipo de separador de plástico que encaja en los riales interiores situados en el fondo de minicanales. El separador está en ello prácticamente suspendido y su plano divisorio está desplazado – con ello se consigue una segregación más efectiva de espacios interiores en minicanales.
- la forma del separador metálico PEP 60/K es parecida al separador PEP 60 – su plano divisorio también está desplazado desde el punto de fijación que se realiza mediante grapas PSK 1. Los separadores PKS 60/K se deben conectar entre sí. Para ello se utiliza un cable de conexión PLSK.
- canales de blindaje SK 40x20 y SK 40x33 aseguran la calidad del blindaje del conducto y sirven del mismo modo que los separadores para dividir espacio interior de minicanales.
?Cuáles son las posibilidades de montaje de tomas de corriente dobles en las cajas de bandeja?
En el surtido de la empresa KOPOS hay varios sistemas de bandejas en las cuales se podrán instalar tomas de corriente dobles. Se trata de LK 80X28 2ZK, LK 80X28 2R, LK 80X28 2ZT y libres de halógenos LK 80X28 2ZKHF a LK 80X28 2ZTHF.
La caja de bandeja LK 80X28 2R permite la instalación de 2 uds de mecanismos (p.ej. tomas simples) o la instalación de un mecanismo y tapa VLK 80/R con caja de bornes. La caja es adecuada también para la toma doble junto con la caja de bornes y tapa VLK 80/2R. Si la caja permite la instalación de una toma de corriente doble, este hecho se indica en el catálogo con el símbolo correspondiente.
?Cuáles son las nuevas clases de combustión de material?
?Cuál es el radio mínimo de recodo de tubos corrugados KOPOFLEX?
?Cuáles son las dimensiones de embalaje de tubos corrugados KOPOFLEX?
KOPOFLEX | Diámetro exterior (mm) | Diámetro interior (mm) | Radio mínimo de recodo (mm) | Embalaje (m/kg) | Dimensión embalaje (cm) |
KF 09040 | 40 | 32 | 230 | 50 / 9,5 | 80 x 25 |
KF 09050 | 50 | 41 | 350 | 50 / 13 | 100 x 30 |
KF 09063 | 63 | 52 | 350 | 50 / 15,7 | 90 x 46 |
KF 09075 | 75 | 61 | 350 | 50 / 18,7 | 120 x 40 |
KF 09090 | 90 | 75 | 400 | 50 / 27 | 125 x 45 |
KF 09110 | 110 | 94 | 400 | 50 / 34,5 | 120 x 70 |
KF 09120 | 120 | 100 | 500 | 50 / 37,5 | 150 x 60 |
KF 09125 | 125 | 108 | 500 | 50 / 39 | 150 x 70 |
KF 09160 | 160 | 136 | 650 | 50 / 46 | 190 x 80 |
KF 09175 | 175 | 150 | 700 | 50 / 64 | 200 x 65 |
?Con cuáles condiciones debe cumplirse al instalar bandejas y cajas de bandejas sobre materiales combustibles?
Las bandejas de instalación eléctrica KOPOS se pueden instalar sobre todos los materiales del grupo de combustión A hasta C3. Sin embargo, debe cumplirse con la condición de que el cable llevado por la bandeja no está en ningún punto prolongado, interrumpido o dotado de bornes.
Las cajas de bandejas se pueden montar sobre superficies de combustión de A hasta C2 directamente. En el caso de montaje sobre un material de combustión C3 es necesario utilizar debajo de la caja un aislante térmico.
?Qué número de conductos podrán contener bandejas y tubos de instalación eléctrica?
Ejemplos de alojamiento están indicados en la tabla donde se calcula con un uso del 60 % de la sección interior.
Más información aquí.
?En qué grupo de combustión pertenece madera?
Los distintos tipos de madera difieren por su composición y propiedades y por eso pertenecen a diferentes grupos. Para más información ponemos un sumario de todos los tipos de materiales más conocidos con la indicación de su clase de combustión.
Más información aquí.
?Cuál es el radio mínimo de recodo de tubos de instalación eléctrica?
El radio mínimo de recodo de tubos de instalación eléctrica KOPOS se indica en milímetros y se refiere al eje central interior del tubo (véase la figura).
Dimensión nominal | Radio mínimo de recodo (mm) | |
UNE-EN | ČSN | |
16 | 60 | |
13,5 | 70 | |
20 | 80 | |
16 | 80 | |
25 | 100 | |
23 | 100 | |
32 | 120 | |
29 | 140 | |
40 | 170 | |
36 | 200 | |
50 | 220 | |
48 | 250 | |
63 | 250 |
?Cómo se define el concepto de autoextinción?
La autoextinción es resistencia a propagación de la llama que se divide según el grupo de productos (cajas, bandejas, tubos). En los distintos grupos es diferente y su definición exacta viene dada por normas correspondientes. En general se puede decir que un producto o un material son autoextinguibles si después de apartarlos de la llama apagarán en un tiempo fijado por la norma.